12MRLDS I&O Manual 026-1307 Rev 3 06-APR-2010
ways.
Navigate to the controllers Input Status screen and
highlight the board and point that you wish to map. Press
F1 to go to the Input Setup screen for that board/point.
Each point will increase incrementally to correspond with
each board. (For example, where the MRLDS is address 1
and the MRLDS address is 100, use board 1, point 1. For
an MRLDS address of 101, use point 2.)
4.4.3 E2/Einstein Controllers
Next, set up the following parameters on the Input
Setup screen:
•Sensor Type: Linear
Low End Point: 0.00000
Select Eng. Units: PPM
HighEnd Point: 4.80000
High Eng. Units: 1200.0000
4.4.4 RMCC Controllers Version
2.1 and Newer
4.4.4.1 REFLECS Setup for IRLDS IIs
Set dip switch 8 to ON and follow the steps for setting
up IRLDS IIs through the REFLECS controller interface:
1. Log on.
2. Press 7 for Configuration to reach the CON-
FIGURATION screen.
Input Definitions should be set here to show how the
sensor control is linked to the zone. The number of devices
and IRLDS IIs are connected to the Gateway and enabled
is the number of address slots the Gateway will use.
3. Press 1 for Input Definitions to reach the
INPUT DEFINITIONS screen.
4. Pressing the down arrow several times will
get you to the input list of SENS01-48. Bd
(board) is the address of the Gateway, Pt
(point) is the zone and allows you to define
where the sensor input comes from.
The board number for the IRLDS II setup is the address
of the Gateway. If there are three or less IRLDS II control-
lers connected to a Gateway, the Gateway address = the
IRLDS II address. However, if there are more than three
IRLDS controllers, the second Gateway address will be the
one entered for the board number, but the IRLDS II con-
trollers are set 1 to 3 on the second Gateway.
5. Press 0 (zero) to go back to the CONFIGU-
RATION screen.
6. Press 7 for I/O Brd Setup to reach the I/O
BOARD MENU screen.
7. Press 2 to Set Device #’s.
The Gateway will react as three 16AI boards. The num-
ber of IRLDS II controllers plus the real number of 16AIs
= the total number of 16AIs to enter in the next step:
8. At the I/O BOARD DEVICE NUMBERS
screen, press the down arrow key to reach
Number 16AI Boards and enter the number
of how many 16AI boards and IRLDS II con-
trollers there are. Press Enter.
9. Arrow down to the I/O BOARD MENU and
press 0 (zero) twice to go back to the MAIN
MENU screen.
10. Press 4 for Sensor Control.
11. Press 2 for Setup--up to 48 sensor control
programs are allowed. Select one of the 48
units and press Enter to reach the SENSOR
SETUP screen.
12. Press the right arrow to move to the Name
Figure 4-20
- Analog Input Screen Settings Example for E2
Page view 17