Emerson ZB Copeland Scroll Technical Information Page 7

  • Download
  • Add to my manuals
  • Print
  • Page
    / 21
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 6
4 C6.1.7/0609-1110/E
2.6 Application range
2.6.1 Qualified refrigerants and oils
IMPORTANT
It is essential that the glide of refrigerant blends is carefully considered when
adjusting pressure and superheat controls.
Oil recharge values can be taken from Copeland Scroll compressors brochures or Copeland®
Brand Products Selection Software.
Unit
HLR13-ZBD30KCE, HLR13-ZBD45K,
HLR13-ZBD58K, HLR13-ZBD76K,
HLR31-ZBDT60KCE, HLR31-ZBDT90KCE,
HLR31-ZBDT116KCE, HLR31-ZBDT152KCE
Qualified refrigerant
R404A
Copeland® Brand Products
standard oil
Emkarate RL 32 3MAF
Qualified servicing oil
Emkarate RL 32 3MAF / MOBIL EAL Arctic 22 CC
Table 1: Qualified refrigerants and oils
2.6.2 Application limits
For application envelopes, please refer to the compressor application envelope available in
Copeland® Brand Products Selection Software.
Medium temperature range
Evaporating temperature from 30°C up to 10°C, condensing temperature range depending on
evaporating temperature. See Copeland® Brand Products Selection Software or literature for
further information.
2.7 Main components description
2.7.1 Compressor
Single-compressor unit
Two-compressor unit
Unit model
Compressor
model
Unit model
Compressor models
HLR13-ZBD30KCE
ZBD30KCE
HLR31-ZBDT60KCE
ZBD30KCE + ZB30KCE
HLR13-ZBD45KCE
ZBD45KCE
HLR31-ZBDT90KCE
ZBD45KCE + ZB45KCE
HLR13-ZBD58KCE
ZBD58KCE
HLR31-ZBDT116KCE
ZBD58KCE + ZB58KCE
HLR13-ZBD58KCE
ZBD76KCE
HLR31-ZBDT152KCE
ZBD76KCE + ZB76KCE
Table 2: Compressor type used in Digital Receiver unit HLR
2.7.2 Liquid receiver
Copeland Scroll Digital Receiver units HLR are equipped with a liquid receiver with:
Rotalock service valve on top of the receiver for liquid outlet line;
3/8’’–14 NPTF connection for relief valve.
Fitting a pressure relief device according to standard EN 378-2 is the responsibility of the
installer.
Model type
Receiver volume (L)
HLR13-ZBD30KCE, HLR13-ZBD45KCE, HLR13-
ZBD58KCE, HLR13-ZBD760KCE
13
HLR31-ZBDT60KCE, HLR31-ZBDT90KCE, HLR31-
ZBDT116KCE, HLR31-ZBDT152KCE
31
Table 3: Receiver volume
It is recommended to charge the system with refrigerant via the Rotalock service valves.
Page view 6